2017年瑞士巴塞尔市发现军团菌感染病例增加,研究对当地供水、两座空调冷却塔分离株(n=60)、2017年临床暴发与非暴发相关分离株(n=8)及2003-2016年历史分离株(n=26)进行全基因组测序和cgMLST分析。结果显示两座冷却塔存在多种菌株,其中一塔的两株分离株与三株2017年临床分离株无等位基因差异,且近十年五株临床分离株与两塔近期分离株cgMLST一致。结论认为当前暴发相关和历史分离株均与冷却塔相关,冷却塔构成菌株可保存多年的复杂环境栖息地。

要点

  • 空调冷却塔可同时存在多种军团菌菌株,cgMLST显示数百个等位基因差异。
  • 一塔两株分离株与三株2017年临床暴发分离株cgMLST无等位基因差异。
  • 近十年五株临床分离株与两塔近期分离株cgMLST一致,提示持续来源。

核心结论

  • 当前暴发相关和历史分离株均与空调冷却塔相关,冷却塔是菌株可保存多年的复杂环境栖息地。

研究设计与样本

  • 流行病学与基于全基因组测序的微生物学调查,纳入环境分离株n=60、2017年临床分离株n=8及2003-2016年历史分离株n=26。

主要发现

  • 两座空调冷却塔均检出多种菌株,cgMLST显示数百个等位基因差异。
  • 一塔两株分离株与三株2017年临床分离株cgMLST无等位基因差异。
  • 近十年五株临床分离株与两塔近期分离株cgMLST一致。

临床怎么用

  • 对军团菌暴发溯源时,可采用WGS和cgMLST高分辨率方法区分环境与临床菌株。
  • 空调冷却塔应作为军团菌持续监测和防控的重点环境源。

以上解读依据论文摘要(全文未开放获取或许可不允许翻译转载)。

原文

IntroductionWater supply and air-conditioner cooling towers (ACCT) are potential sources of Legionella pneumophila infection in people. During outbreaks, traditional typing methods cannot sufficiently segregate L. pneumophila strains to reliably trace back transmissions to these artificial water systems. Moreover, because multiple L. pneumophila strains may be present within these systems, methods to adequately distinguish strains are needed. Whole genome sequencing (WGS) and core genome multilocus sequence typing (cgMLST), with their higher resolution are helpful in this respect. In summer 2017, the health administration of the city of Basel detected an increase of L. pneumophila infections compared with previous months, signalling an outbreak.AimWe aimed to identify L. pneumophila strains populating suspected environmental sources of the outbreak, and to assess the relations between these strains and clinical outbreak strains.MethodsAn epidemiological and WGS-based microbiological investigation was performed, involving isolates from the local water supply and two ACCTs (n = 60), clinical outbreak and non-outbreak related isolates from 2017 (n = 8) and historic isolates from 2003-2016 (n = 26).ResultsIn both ACCTs, multiple strains were found. Phylogenetic analysis of the ACCT isolates showed a diversity of a few hundred allelic differences in cgMLST. Furthermore, two isolates from one ACCT showed no allelic differences to three clinical isolates from 2017. Five clinical isolates collected in the Basel area in the last decade were also identical in cgMLST to recent isolates from the two ACCTs.ConclusionCurrent outbreak-related and historic isolates were linked to ACCTs, which form a complex environmental habitat where strains are conserved over years.

来源:Euro Surveill,查看原文。版权归原作者所有。

引用

  1. Wüthrich D, Gautsch S, Spieler-Denz R, et al. Air-conditioner cooling towers as complex reservoirs and continuous source of Legionella pneumophila infection evidenced by a genomic analysis study in 2017, Switzerland. Euro Surveill. 2019. PMID: 30696527. doi:10.2807/1560-7917.ES.2019.24.4.1800192