指南与共识术前评估与围术期医学气道管理

重症监护病房与手术室消防安全及紧急疏散指南

Fire safety and emergency evacuation guidelines for intensive care units and operating theatres: for use in the event of fire, flood, power cut, oxygen supply failure, noxious gas, structural collapse or other critical incidents: Guidelines from the Association of Anaesthetists and the Intensive Care Society.
指南 / 共识 · Anaesthesia · 2021-05-13

本指南由麻醉医师协会与重症监护学会制定,针对ICU和手术室在火灾、洪水、断电、氧供故障等紧急情况下的疏散问题。指南提出建筑设计应纳入手动火灾报警点、氧气区域阀门、多出口路线等强制消防特征,并要求制定定制化疏散计划、开展年度实操培训、启动网络化应急响应及事后调查与员工支持。

要点

  • 新建或翻新ICU和手术室应纳入手动火灾报警点、氧气关断阀、独立分区隔离、多出口路线等强制消防设计。
  • 每个ICU和手术室应制定定制化紧急疏散计划和路线图,并随时可用。
  • 员工入职及每年须接受所在临床区域的消防疏散实操培训,包括走场演练或模拟训练。

核心结论

  • ICU和手术室紧急疏散虽罕见但风险高,可通过建筑设计、定制化预案、员工培训和网络化响应改善管理结局。

研究设计与样本

  • 由麻醉医师协会与重症监护学会制定的指南,基于专家共识提出推荐条款。

主要发现

  • 指南强调建筑设计应包含手动火灾报警点、氧气关断阀(区域阀门服务单元)、独立分区隔离能力、多出口路线、小隔间或单间、ICU首选地面层及与手术室互联路线、临床与非临床区域分离。

关键数值与推荐

  • ICU和手术室应具备定制化紧急疏散计划和路线图并随时可用。
  • 员工应在入职时及每年作为强制培训的一部分,接受所在临床区域的消防疏散实操培训,包括走场演练或模拟训练,并熟悉手动火灾报警点、灭火器位置、疏散路线及区域阀门服务单元的位置与操作。
  • 每班负责人员应能选择操作灭火器并领导疏散。
  • 紧急疏散后应启动网络化响应,包括必要时将患者转运至其他ICU。
  • 应进行全面调查,并为员工提供持续支持和随访。

临床怎么用

  • 麻醉科智能体医生应熟悉所在ICU/手术室的疏散路线图、手动火灾报警点、灭火器及区域阀门服务单元位置。
  • 每班负责人应具备操作灭火器和领导疏散的能力。
  • 紧急疏散后应配合启动网络化响应,参与患者转运及事后调查与员工支持。

以上解读依据论文摘要(全文未开放获取或许可不允许翻译转载)。

原文

The need to evacuate an ICU or operating theatre complex during a fire or other emergency is a rare event but one potentially fraught with difficulty: Not only is there a risk that patients may come to harm but also that staff may be injured and unable to work. Designing newly-built or refurbished ICUs and operating theatre suites is an opportunity to incorporate mandatory fire safety features and improve the management and outcomes of such emergencies: These include well-marked manual fire call points and oxygen shut off valves (area valve service units); the ability to isolate individual zones; multiple clear exit routes; small bays or side rooms; preference for ground floor ICU location and interconnecting routes with operating theatres; separate clinical and non-clinical areas. ICUs and operating theatre suites should have a bespoke emergency evacuation plan and route map that is readily available. Staff should receive practical fire and evacuation training in their clinical area of work on induction and annually as part of mandatory training, including 'walk-through practice' or simulation training and location of manual fire call points and fire extinguishers, evacuation routes and location and operation of area valve service units. The staff member in charge of each shift should be able to select and operate fire extinguishers and lead an evacuation. Following an emergency evacuation, a network-wide response should be activated, including retrieval and transport of patients to other ICUs if needed. A full investigation should take place and ongoing support and follow-up of staff provided.

来源:Anaesthesia,查看原文。版权归原作者所有。

引用

  1. Kelly FE, Bailey CR, Aldridge P, et al. Fire safety and emergency evacuation guidelines for intensive care units and operating theatres: for use in the event of fire, flood, power cut, oxygen supply failure, noxious gas, structural collapse or other critical incidents: Guidelines from the Association of Anaesthetists and the Intensive Care Society. Anaesthesia. 2021. PMID: 33984872. doi:10.1111/anae.15511

供执业医师工作参考,不替代临床判断;数值与分级以指南原文为准。